Zobrazit minimální záznam

dc.contributor.authorKřivý, Vít
dc.contributor.authorVašek, Zdeněk
dc.contributor.authorVacek, Miroslav
dc.contributor.authorMynarzová, Lucie
dc.date.accessioned2022-07-15T11:03:47Z
dc.date.available2022-07-15T11:03:47Z
dc.date.issued2022
dc.identifier.citationMaterials. 2022, vol. 15, issue 9, art. no. 3397.cs
dc.identifier.issn1996-1944
dc.identifier.urihttp://hdl.handle.net/10084/146394
dc.description.abstractThe article dealt with the load-bearing capacity and durability of power line lattice towers designed from weathering steel. Attention was paid in particular to the bolted lap joints. The article evaluates the static and corrosion performance of bolted lap joints in long-term operating towers, and also presents and evaluates design measures that can be applied in the design of new lattice towers, or in the reconstruction of already operating structures. Power line lattice towers are the most extensive realization of weathering steel in the Czech Republic. On the basis of the inspections carried out to evaluate the working life of the transmission towers in operation, it can be stated that a sufficiently protective layer of corrosion products generally developed on the bearing elements of the transmission towers. However, the development of crevice corrosion at the bolted joints of the leg members is a significant problem. In this paper, the corrosion damage of bolted joints was evaluated considering two basic aspects: (1) the influence of crevice corrosion on the bearing capacity of the bolted joint was evaluated, using experimental testing and based on analytical and numerical calculations; (2) appropriate design measures applicable to the rehabilitation of developed crevice corrosion of in-service structures, or the elimination of crevice corrosion in newly designed lattice towers, was evaluated. Calculation analyses and destructive tests of bolted joints show that the development of corrosion products in the crevice does not have a significant effect on the bearing capacity of the joint, provided that there is no significant corrosion weakening of the structural elements, and bolts of class 8.8 or 10.9 are used. The results of the long-term experimental programme, and the experience from the rehabilitations carried out, show that, thanks to appropriate structural measures, specified in detail in the paper, the long-term reliable behaviour of the lattice towers structures is ensured.cs
dc.language.isoencs
dc.publisherMDPIcs
dc.relation.ispartofseriesMaterialscs
dc.relation.urihttps://doi.org/10.3390/ma15093397cs
dc.rights© 2022 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.cs
dc.rights.urihttp://creativecommons.org/licenses/by/4.0/cs
dc.subjectsteel structurescs
dc.subjectcrevice corrosioncs
dc.subjectlattice towerscs
dc.subjectbolted lap jointscs
dc.subjectweathering steelcs
dc.subjectexperimental testscs
dc.subjectnumerical modellingcs
dc.titleCorrosion damage to joints of lattice towers designed from weathering steelscs
dc.typearticlecs
dc.identifier.doi10.3390/ma15093397
dc.rights.accessopenAccesscs
dc.type.versionpublishedVersioncs
dc.type.statusPeer-reviewedcs
dc.description.sourceWeb of Sciencecs
dc.description.volume15cs
dc.description.issue9cs
dc.description.firstpageart. no. 3397cs
dc.identifier.wos000799329700001