Design of Electrical System for Offshore Wind Power Plant (OWPP)
Loading...
Downloads
3
Date issued
Journal Title
Journal ISSN
Volume Title
Publisher
Vysoká škola báňská - Technická univerzita Ostrava
Location
Signature
License
Abstract
The paper proposes a novel Optimum Fre-
quency AC (OFAC) transmission system for reduc-
ing investment and operational cost of Electric Sys-
tem (ES) - integrating Offshore Wind Farm (OWF)
to the onshore grid. Optimum operational frequency
for ES is an inherent characteristic of the trade-off be-
tween its investment and operational cost. The paper
presents a comprehensive methodology for the design
of ES based on Life Cost Analysis using a Generic Al-
gorithm. For the given offshore wind farm, alternative
designs for ES are generated for different operational
frequencies. Power system components of standard rat-
ings are used for the designs. All the designs are evalu-
ated in terms of Net Present Values (NPV) and the de-
sign with maximum NPV is selected as the optimum
solution. For 200 MW OWF, optimum operational fre-
quencies are obtained as 50, 35, 25, and 50/3 Hz for
offshore distances of 50, 100, 150, and 200 km, respec-
tively. The results show that for 200 MW the feasible
range for OFAC is 100–150 km and provides the saving
of 5–10 % as compared to High Voltage AC (HVAC)
and Low-Frequency AC (LFAC). The results further
indicate that for large-scale wind farms the saving in-
creases substantially and the feasible range is reduced.
It concludes that OFAC is an economical alternative
to HVAC and LFAC for integrating large-scale OWF
to the onshore grid and provides a new dimension for
promoting Offshore Wind Power Plant (OWPP)
Description
Subject(s)
cost model, FFTS, offshore wind farm, optimum frequency
Citation
Advances in electrical and electronic engineering. 2022, vol. 20, no. 2, p. 131 - 142 : ill.