Kompenzace účiníku a eliminace negativních zpětných vlivů na napájecí síť u elektrické obloukové pece
Loading...
Downloads
7
Date issued
Authors
Rozehnal, Petr
Journal Title
Journal ISSN
Volume Title
Publisher
Vysoká škola báňská - Technická univerzita Ostrava
Location
ÚK/Sklad diplomových prací
Signature
200901869
Abstract
This graduation thesis deals with the varieties negative effects, which rise from operations of Electrical Arc Furnace and their elimination by Static var compensation equipment (SVC). SVC gains capacitive reactive power from the capacitor banks (filters), which are connected to supply network. Leading reactive power is continuously controlled by means of antiparallel thyristor valve, which regulates current of decompesation reactor, connected in parallel to capacitor banks.
The project of Static var compensation is solved for steel-making Electric Arc Furnace, with furnace transformer 42 MVA, connected to supply network 22 kV. This design of SVC in full range, overreaches the framework of this graduation thesis. Therefore only some parts were elaborated in detail, for example the calculation of reactive power, calculation of frequency response of filters, harmonic voltages and voltage fluctuation (flicker severity).
Description
Subject(s)
filter, thyristor valve. , reactor, compensating power, PQ circle diagram, capacitor bank, reactive power compensation, voltage fluctuation, frequency response of network, harmonic voltage, electrical arc furnace