Zobrazit minimální záznam

dc.contributor.authorBoháč, Leoš
dc.contributor.authorVodrážka, Jiří
dc.date2013
dc.date.accessioned2014-01-14T08:27:29Z
dc.date.available2014-01-14T08:27:29Z
dc.date.issued2013
dc.identifier.citationAdvances in electrical and electronic engineering. 2013, vol. 11, no. 5, p. 321-326 : ill.cs
dc.identifier.issn1804-3119
dc.identifier.issn1336-1376
dc.identifier.urihttp://hdl.handle.net/10084/101392
dc.description.abstractThe paper analyses and experimentally verifies deployment of Ethernet based network technology to enable fault tolerant and timely exchange of data among a number of high voltage protective relays that use proprietary serial communication line to exchange data in real time on a state of its high voltage circuitry facilitating a fast protection switching in case of critical failures. The digital serial signal is first fetched into PCM multiplexer where it is mapped to the corresponding E1 (2 Mbit/s) time division multiplexed signal. Subsequently, the resulting E1 frames are then packetized and sent through Ethernet control LAN to the opposite PCM demultiplexer where the same but reverse processing is done finally sending a signal into the opposite protective relay. The challenge of this setup is to assure very timely delivery of the control information between protective relays even in the cases of potential failures of Ethernet network itself. The tolerance of Ethernet network to faults is assured using widespread per VLAN Rapid Spanning Tree Protocol potentially extended by 1+1 PCM protection as a valuable option.cs
dc.format.extent1632138 bytes
dc.format.mimetypeapplication/pdf
dc.language.isoencs
dc.publisherVysoká škola báňská - Technická univerzita Ostravacs
dc.relation.ispartofseriesAdvances in electrical and electronic engineeringcs
dc.relation.urihttp://advances.utc.sk/index.php/AEEE/article/download/869/886cs
dc.rights© Vysoká škola báňská - Technická univerzita Ostrava
dc.rightsCreative Commons Attribution 3.0 Unported (CC BY 3.0)
dc.subjectE1cs
dc.subjectPCMcs
dc.subjectprotective switchcs
dc.subjectRSTPcs
dc.subjectsmart gridcs
dc.subjecttime sensitive applicationscs
dc.titleFault tolerant ethernet based network for time sensitive applications in electrical power distribution systemscs
dc.typearticlecs
dc.rights.accessopenAccess
dc.type.versionpublishedVersioncs
dc.type.statusPeer-reviewedcs


Soubory tohoto záznamu

Tento záznam se objevuje v následujících kolekcích

  • AEEE. 2013, vol. 11 [58]
  • OpenAIRE [5085]
    Kolekce určená pro sklízení infrastrukturou OpenAIRE; obsahuje otevřeně přístupné publikace, případně další publikace, které jsou výsledkem projektů rámcových programů Evropské komise (7. RP, H2020, Horizon Europe).

Zobrazit minimální záznam