Zobrazit minimální záznam

dc.contributor.authorRaichura, Maulik
dc.contributor.authorChothani, Nilesh
dc.contributor.authorPatel, Dharmesh
dc.date.accessioned2020-10-12T12:28:12Z
dc.date.available2020-10-12T12:28:12Z
dc.date.issued2020
dc.identifier.citationAdvances in electrical and electronic engineering. 2020, vol. 18, no. 3, p. 180 - 189 : ill.cs
dc.identifier.issn1336-1376
dc.identifier.issn1804-3119
dc.identifier.urihttp://hdl.handle.net/10084/142299
dc.description.abstractThe differential relaying scheme is universally adopted as the main protection for power transformer. In certain situations, like temporary over-fluxing, this differential protection may malfunction. This is due to unbalance in primary and secondary current, as the saturated core does not reflect equal ampere-turn on either side. This article presents detection of over-fluxing condition against the internal fault based on the fifth harmonic component of differential current. As per the estimated level of the fifth harmonic concerning the fundamental component of differential current, the pickup setting of percentage bias characteristic will be modified to avoid maloperation. Once the over-flux condition is sensed, the algorithm activates timer-based V/f protection to protect the equipment. The proposed algorithm is validated on PSCAD software and after the collection of data, MATLAB software is used for further validation. The proposed algorithm is validated under various test conditions like normal load, external fault, internal fault, and over-fluxing. It is observed that the algorithm accurately detects internal fault in the transformer or blocks the relay operation under momentary over-fluxing situations. Further, to assassinate the competency of the proposed scheme, a practical test is performed on a single-phase transformer available in laboratory. The data for various test cases are captured with the help of DSO, and the collected data has been migrated to computer where the proposed algorithm is examined. After analyzing all the results, it is cleared that the proposed algorithm can prevent transformer isolation during momentary over-fluxing conditions.cs
dc.languageNeuvedenocs
dc.language.isoencs
dc.publisherVysoká škola báňská - Technická univerzita Ostravacs
dc.relation.ispartofseriesAdvances in electrical and electronic engineeringcs
dc.relation.urihttp://dx.doi.org/10.15598/aeee.v18i3.3833
dc.rights© Vysoká škola báňská - Technická univerzita Ostrava
dc.rightsAttribution-NoDerivatives 4.0 International*
dc.rights.urihttp://creativecommons.org/licenses/by-nd/4.0/*
dc.subjectdifferential relaycs
dc.subjectfaultcs
dc.subjectharmonic componentscs
dc.subjectMDFTcs
dc.subjectover-fluxingcs
dc.subjectpower transformercs
dc.titleImproved Transformer Differential Protection by Adaptive Pickup Setting during Momentary Over-Fluxing Conditioncs
dc.typearticlecs
dc.identifier.doi10.15598/aeee.v18i3.3833
dc.rights.accessopenAccess
dc.type.versionpublishedVersion
dc.type.statusPeer-reviewed


Soubory tohoto záznamu

Tento záznam se objevuje v následujících kolekcích

Zobrazit minimální záznam

© Vysoká škola báňská - Technická univerzita Ostrava
Kromě případů, kde je uvedeno jinak, licence tohoto záznamu je © Vysoká škola báňská - Technická univerzita Ostrava