Diagnostics of hydrogen-containing mixture compression by a two-stage piston compressor with cooling demand prediction
Loading...
Downloads
5
Date issued
Journal Title
Journal ISSN
Volume Title
Publisher
MDPI
Location
Signature
License
Abstract
The present article describes the diagnostics of a compressor that is compressing a mixture of H-2 and N-2 on the basis of the results that were obtained by operational measurements of the flow rates and temperatures at selected compressor sites, as well as of the acoustic pressure levels during the full loading thereof. The obtained data were subsequently used to determine the limit conditions of the compressor operations in terms of the cooling capacity. A thermodynamic analysis of the compression of the H-2/N-2 gas mixture was carried out with subsequent heat and energy flow calculation and the determination of the minimum cooling water flow rate that is required to ensure the continuous compressor operations.
Description
Subject(s)
compressor, diagnostics, operating experiment, minimum cooling capacity
Citation
Applied Sciences. 2018, vol. 8, issue 4, art. no. 625.