Evaluating eco-friendly refrigerant alternatives for cascade refrigeration systems: A thermoeconomic analysis

dc.contributor.authorShanmugasundar, G.
dc.contributor.authorLogesh, Kamaraj
dc.contributor.authorČep, Robert
dc.contributor.authorRoy, Ranendra
dc.date.accessioned2024-02-13T09:17:32Z
dc.date.available2024-02-13T09:17:32Z
dc.date.issued2023
dc.description.abstractA simple vapor-compression refrigeration system becomes ineffective and inefficient as it consumes a huge energy supply when operating between large temperature differences. Moreover, the recent Kigali amendment has raised a concern about phasing out some hydrofluorocarbon refrigerants due to their impact on the environment. In this paper, a numerical investigation is carried out to compare the performance of a cascade refrigeration system with two environmentally friendly refrigerant combinations, namely, R170–R404A and R41–R404A. Refrigerant R170, from the hydrocarbon category, and refrigerant R41, from the hydrofluorocarbon category, are separately chosen for the low-temperature circuit due to their similar thermophysical properties. On the other hand, refrigerant R404A is selected for the high-temperature circuit. An attempt is made to replace refrigerant R41 with refrigerant R170 as a possible alternative. The condenser temperature is kept constant at 40 ◦C, and the evaporator temperature is varied from −60 ◦C to −30 ◦C. The mathematical model developed for the cascade refrigeration system is solved using Engineering Equation Solver (EES). The effect of evaporator temperature on different performance parameters such as the COP, exergetic efficiency, and total plant cost rate is evaluated. The predicted results show that the thermoeconomic performance of the R170–R404A-based system is marginally lower compared to that of the R41–R404A-based system. The system using refrigerant pair R170–R404A has achieved only a 2.4% lower exergetic efficiency compared to the system using R41–R404A, with an increase in the annual plant cost rate of only USD 200. As the global warming potential (GWP) of R170 is less than that of R41, and R170 belongs to the hydrocarbon category, the use of the R170–R404A combination in a cascade refrigeration system can be recommended as an alternative to R41–R404A.cs
dc.description.firstpageart. no. 1622cs
dc.description.issue6cs
dc.description.sourceWeb of Sciencecs
dc.description.volume11cs
dc.identifier.citationProcesses. 2023, vol. 11, issue 6, art. no. 1622.cs
dc.identifier.doi10.3390/pr11061622
dc.identifier.issn2227-9717
dc.identifier.urihttp://hdl.handle.net/10084/152172
dc.identifier.wos001015924300001
dc.language.isoencs
dc.publisherMDPIcs
dc.relation.ispartofseriesProcessescs
dc.relation.urihttps://doi.org/10.3390/pr11061622cs
dc.rights© 2023 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.cs
dc.rights.accessopenAccesscs
dc.rights.urihttp://creativecommons.org/licenses/by/4.0/cs
dc.subjectcascade refrigeration systemcs
dc.subjectR170cs
dc.subjectco-efficient of performancecs
dc.subjectexergetic efficiencycs
dc.subjectannual plant costcs
dc.titleEvaluating eco-friendly refrigerant alternatives for cascade refrigeration systems: A thermoeconomic analysiscs
dc.typearticlecs
dc.type.statusPeer-reviewedcs
dc.type.versionpublishedVersioncs

Files

Original bundle

Now showing 1 - 1 out of 1 results
Loading...
Thumbnail Image
Name:
2227-9717-2023v11i6an1622.pdf
Size:
2.87 MB
Format:
Adobe Portable Document Format
Description:

License bundle

Now showing 1 - 1 out of 1 results
Loading...
Thumbnail Image
Name:
license.txt
Size:
718 B
Format:
Item-specific license agreed upon to submission
Description: