Determination of network impedance at the place of single-phase load connection

Loading...
Thumbnail Image

Downloads

2

Date issued

Authors

Paleček, Josef
Kolář, Václav
Stýskala, Vítězslav

Journal Title

Journal ISSN

Volume Title

Publisher

Sigma Not

Location

Není ve fondu ÚK

Signature

Abstract

The article deals with asymmetry in three phase systems and its relations to single-phase load and short circuit power. A ratio is derived between the coefficient of the voltage asymmetry u, the single-phase load S1f and the three-phase short circuit power. Further is shown an idea to investigate short circuit power from measured values of u and S1f. The results of verification measurement which was carried out in a traction transformer substation of electric railways 25 kV; 50 Hz of the Czech railways are mentioned in the article too.

Description

Subject(s)

asymmetry, short circuit power, traction, asymetria sieci trójfazowej, moc zwarciowa

Citation

Przegląd elektrotechniczny. 2012, r. 88, nr. 8, s. 264-265.